Mohammad Alhamad, CFPS
Nov 2

Clean Agent Hold Time and Room Integrity Test Explained

Hold time is how long a clean agent stays in the room at a concentration that still controls the fire. NFPA 2001 §5.6 requires at least 85% of the adjusted minimum design concentration at the highest level of protected content for 10 minutes, or until trained personnel respond. A room integrity test, also called a door fan test, checks this without discharging any gas.

FREE TOOL FOR FIRE ENGINEERS
🧮 Clean Agent & CO₂ Calculator
Confirm the agent quantity and peak concentration before the door fan test. Enter the room, pick the hazard class and get the agent quantity, peak concentration and NOAEL check in seconds.
Open the free calculator →
▶  WATCH: How to Calculate FM-200 System Gas Quantity

The test measures how leaky the room is and predicts how fast the agent will drain out. If the predicted hold time is too short, the room fails and the leaks must be sealed. To get the agent quantity first, use the free FM-200, Novec 1230 and CO2 calculator.

Why Hold Time Matters

A clean agent system must discharge within 10 seconds to reach 95% of the minimum design concentration. Then the room must keep the agent long enough to stop the fire from starting again.

The agent and air mixture is heavier than normal air. It leaks out through low openings while fresh air comes in high. The line between the agent mixture and fresh air moves down over time.

If the line drops below the top of your protected equipment before 10 minutes, the top of the racks is no longer protected, and a hot component can re-ignite. That is why hold time is measured at the height of the highest protected content, not the floor.

How a Door Fan Test Works

The door fan test follows the enclosure integrity procedure in NFPA 2001. Here is what happens, in simple terms:

  1. The technician fits a temporary panel with a calibrated fan into an open doorway.
  2. The fan blows air into the room, then pulls air out of it.
  3. Gauges record the air flow and the pressure difference across the room boundary.
  4. Software works out the total leakage area of the room from these readings.
  5. Using the agent type, concentration, room height and protected height, the software predicts the hold time.

The result is a pass or fail against the §5.6 requirement. The report also shows the leakage area. Because no agent is discharged, you can repeat the test after each round of sealing.

Common Leakage Sources

Most failed tests come from the same few places.

Location Typical leak Usual fix
Cable penetrations Open sleeves, cable trays through walls, unsealed conduits Seal with a fire-rated sealant or a listed penetration system
Ceiling tiles Lay-in tiles that lift or are missing, with walls that stop at the false ceiling Extend walls to the slab, or seal the ceiling void as its own protected volume
Doors Gaps at the bottom and sides, damaged seals, missing closers Fit drop seals and perimeter seals, repair closers
HVAC dampers Dampers that do not close on discharge, leaky blades, open ducts Fit tight-closing dampers interlocked with the suppression panel
Raised floor Gaps at the perimeter, cable cut-outs, open floor grilles Seal the perimeter and cut-outs, check floor void boundaries
Walls Unpainted block walls, gaps at the slab, pipe sleeves Seal or paint porous surfaces, fill gaps at the slab

Low leaks let the heavy agent mixture drain out. High leaks let fresh air in. Treat both.

What to Check Before the Test

Before you book the tester for a clean agent room integrity test, confirm:

  • All construction work in and around the room is finished.
  • All doors close and latch, with seals in place.
  • HVAC dampers close as they would on a real discharge.
  • The ceiling void and raised floor boundaries are complete.
  • You have the design data: agent, design concentration, room volume, room height and the height of the highest protected content.
  • The facility team knows the test date and keeps the doors closed.

Design Factors, Voids and Hold Time

Hold time links back to the design. Three points cause confusion on site.

Voids are separate volumes. The ceiling void and the raised floor void are calculated as separate volumes, each with its own nozzles. Their boundaries affect leakage. A leaky floor void drains agent from the room above it.

Design factors do not fix leaks. NFPA 2001 §5.5.3.2 gives additional design factors for unclosable openings, acid gas control, re-ignition and obstructions. These add agent to cover a known condition. They do not replace good sealing.

More agent is not a free fix. Adding gas to a failed room also raises the peak concentration. The NOAEL is 9.0% for FM-200 and 10% for Novec 1230. In a normally occupied room, you cannot go above NOAEL without means to limit exposure. Seal the room first, then re-check the peak.

Also watch for the double safety factor error: 7.0 × 1.35 = 9.45% for FM-200 Class C is already above the 9.0% NOAEL.

For a clear walk-through of how the base FM-200 quantity is built, watch How to Calculate FM200 System Gas Quantity.

Practical Site Checklist

  1. Get the design concentration, net volume and protected height from the approved design.
  2. Walk the room, the ceiling void and the floor void with a torch.
  3. Mark every open penetration, gap and missing tile.
  4. Test each door: closer, latch, bottom seal and side seals.
  5. Confirm HVAC shutdown and damper closure with the BMS or HVAC contractor.
  6. Seal everything, then run the door fan test.
  7. If it fails, use the report's leakage area to find and seal the remaining leaks, then re-test.
  8. Keep the final report with the system records. Re-check the room after any building works, new cables or HVAC changes.
⚡ TRY IT NOW
Before the integrity test, confirm your agent quantity and peak concentration in the TPFE Clean Agent Calculator. If you change the design concentration after a failed test, run the numbers again so you stay below NOAEL.
Calculate your room →

Clean Agent Hold Time FAQ

What is the required hold time for a clean agent system?
NFPA 2001 §5.6 requires at least 85% of the adjusted minimum design concentration at the highest level of protected content for 10 minutes, or until trained personnel respond.
What is a room integrity test?
It is a door fan test. A calibrated fan pressurises and depressurises the room, software calculates the leakage area, and it predicts how long the agent will hold. No agent is discharged.
What are the most common reasons a room fails the door fan test?
Open cable penetrations, lifted or missing ceiling tiles, poor door seals, HVAC dampers that do not close, and gaps around raised floors and walls.
Can I add more agent instead of sealing the room?
Not as a first step. More agent raises the peak concentration, which must stay within the NOAEL limits for occupied rooms. Seal the leaks first, then re-check the design.
Are ceiling and floor voids included in the integrity test?
The voids are calculated as separate volumes with their own nozzles, but their boundaries affect leakage. A leaky floor or ceiling void can drain agent from the main room.

Related reading: Anti-Vortex Plate in Fire Pump Suction Tanks: What It Does

CFPS EXAM PREPARATION COURSE
🎓 Hold time and room integrity are on the CFPS exam
Hold time, enclosure integrity and agent limits are tested topics in the CFPS exam. Our CFPS Exam Preparation Course takes you through the 21st Edition handbook section by section, with 600+ practice questions, 3 full mock exams and a CFPS exam simulator. USD 350, with 12 months access.
Join the CFPS exam preparation course →

Sources: NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems and NFPA 12, Standard on Carbon Dioxide Extinguishing Systems. Values are from NFPA 2001 (2018 edition) and NFPA 12. Always check the edition adopted by your Authority Having Jurisdiction and the listed manufacturer's design manual.